Mercury 2 & Intuitive Mercury Mini-Pack Installation Guide
Parameter Descriptions
Transducer value below zero
Pressure target, control will try to maintain this pressure
Set-point above the target, used to obtain a “dead-band”
Set-point above the target, used to obtain a “dead-band”
Number of stages in the system
Delay time between stages on
Delay time between stages off
The following will occur in the event of pressure transducer fault.
If set to On then all Compressors or Fans will turn On in the event of a transducer failure. If set to Off then
all Compressors or Fans will turn Off in the event of a transducer failure.
Time controller is running (in 1000 x hours) before the service icon (Spanner icon) comes on. Reset the
spanner icon to off by changing this parameter to 0 and then back to the desired service interval.
This is an offset that is added to the target pressure when using the Data Manager Energy feature Pack
Optimisation. For example if target pressure is 2.1 Bar and Optimise Limit set to 0.5 Bar. The remote
optimise command will only be able to optimise the current suction setpoint up to a maximum of 2.6 Bar
Selects between Fixed or Floating. For Condenser control only.
Fixed uses the set-point parameter as its target (P-03)
Floating uses the temperature of a selected probe converted to a pressure as the set-point
Selects the probe that measures the “floating” temperature
(Note : This would be fitted to the Air On of the Condenser)
See note : Floating Head Pressure
Stops the floating pressure target from going below this level
Stops the floating pressure target from going above this level
Allows for an offset to be added to the ambient temperature probe used in the “floating” set-point feature.
Delay before HP and LP alarms are signalled
LP alarm set-point, stage off when reached
Point at which LP Shutdown alarm is generated. Note as soon as the LP Shutdown setpoint is reached
any Compressor/Condenser stages, for the associated section, still operating will go off immediately and
does not wait for the LP Shutdown alarm to be created.
Status Fault 1
Status Fault 5
Used to select the type of input required
Time delay before status faults are activated
Time delay before general faults are activated
Used to program the temperature to pressure conversion for floating pressure use.
Used to program the temperature to pressure conversion for floating pressure use.
Used to program the temperature to pressure conversion for floating pressure use.
Used to program the temperature to pressure conversion for floating pressure use.
Used to program the temperature to pressure conversion for floating pressure use.
Used to program the temperature to pressure conversion for floating pressure use.
Stage 1 Relay 1
Stage 5 Relay 5
Select the output for this stage
Restores factory set points