Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 3 M & E Installation Guide
Example of resistor fitted on a probe input.
Switched Resistor Example Wiring
Installation & Dimensions
Panel Cut-out and Clearances
There is no requirement for forced cooling ventilation
No protective Earth is required and none should be fitted
The host equipment must provide a suitable external over-current protection device such
as: -
Fuse: 2A 240 Vac Anti-surge (T) HRC conforming to IEC 60127
2A, 240 VAC Type C conforming to BS EN 60898
Relays 1 - 4 Mechanical Type (M) - Exclusive common
6A Resistive (CosØ = 1)
2A Inductive ( CosØ = 0.4)
Relay 1 Solid State Type (E) - Exclusive common
250Vac (ac only, will not switch dc)
Relay 5 Mechanical Type (M&E) – Exclusive common
3A (non inductive), COS=0.4 2A (inductive load) 200,000 operations
For compliance with the LVD, All relay commons must be at the same potential as the supply voltage
3.01K Ohms (for PTC or NTC type probes)
4-20mA current loop, uses the 12 Vdc output to feed the pressure transducer See wiring
Connect to remote switch or relay